Alarm Panel Battery Backup Calculator

Size the standby battery for an intrusion alarm system: add the panel, keypads, detectors and sirens, choose your required standby time, and get the battery Ah โ€” with the alarm-condition load included.

System devices

DeviceQtyStandby mAAlarm mA

Check ULC-S304 / UL requirements and your monitoring contract.

Battery required

โ€”
minimum battery capacity โ†’ โ€”
Total standby currentโ€”
Total alarm currentโ€”
Standby consumptionโ€”
Alarm consumptionโ€”
Suggested batteryโ€”
Includes a 25% aging factor. Most residential panels fit up to a 7โ€“8 Ah battery; larger capacities need bigger cans or auxiliary supplies.
ad slot

What do you need next?

LVToolbox Pro

Ready to quote the whole access job?

Use the free calculators for quick field checks. Then open LVToolbox Pro to lay out doors, readers and controllers, build your price, and send a professional proposal.

Open LVToolbox Pro โ†’

AMT Systems Ltd. ยท Toronto & GTA

Prefer a professional to handle it?

AMT Systems can assess, design, quote, and install access control and alarm systems across Toronto and the GTA.

Get a Free Quote from AMT Systems โ†’

Typical intrusion device current draw

DeviceStandbyIn alarm
Alarm panel (main board)100โ€“150 mA150โ€“200 mA
LCD/touch keypad60โ€“120 mA120โ€“160 mA
PIR motion detector10โ€“25 mA25 mA
Glassbreak detector20โ€“30 mA35 mA
Door/window contact (wired)~0 mA~0 mA
Indoor siren0 mA300โ€“500 mA
Outdoor siren/bell0โ€“20 mA750โ€“2000 mA
Zone expander / bus module30โ€“65 mA65 mA
Cellular/IP communicator60โ€“100 mA250 mA (transmitting)

The siren is the battery killer

Standby math is easy to pass and alarm math is where designs fail: an outdoor siren pulling 1.5 A will flatten a marginal battery in minutes at the exact moment you need the communicator transmitting. That's why the standard formula reserves capacity for a full alarm event after the standby period has already drained the battery.

Frequently asked questions

How is battery capacity calculated?

Ah = (standby current ร— standby hours) + (alarm current ร— alarm time), ร— 1.25 aging factor. This calculator does exactly that.

How many hours of standby are required?

Commonly 4 h for monitored commercial, 24 h for residential/unmonitored โ€” but the binding number comes from the applicable standard (ULC-S304 in Canada, UL in the US) and your monitoring contract.

Why do alarm batteries fail after 3โ€“4 years?

SLA batteries age chemically on float charge regardless of use. Replace them proactively every 3โ€“5 years โ€” don't wait for the low-battery trouble signal during an outage.