Alarm Panel Battery Backup Calculator
Size the standby battery for an intrusion alarm system: add the panel, keypads, detectors and sirens, choose your required standby time, and get the battery Ah โ with the alarm-condition load included.
System devices
| Device | Qty | Standby mA | Alarm mA |
|---|
Check ULC-S304 / UL requirements and your monitoring contract.
Battery required
What do you need next?
LVToolbox Pro
Ready to quote the whole access job?
Use the free calculators for quick field checks. Then open LVToolbox Pro to lay out doors, readers and controllers, build your price, and send a professional proposal.
Open LVToolbox Pro โAMT Systems Ltd. ยท Toronto & GTA
Prefer a professional to handle it?
AMT Systems can assess, design, quote, and install access control and alarm systems across Toronto and the GTA.
Get a Free Quote from AMT Systems โTypical intrusion device current draw
| Device | Standby | In alarm |
|---|---|---|
| Alarm panel (main board) | 100โ150 mA | 150โ200 mA |
| LCD/touch keypad | 60โ120 mA | 120โ160 mA |
| PIR motion detector | 10โ25 mA | 25 mA |
| Glassbreak detector | 20โ30 mA | 35 mA |
| Door/window contact (wired) | ~0 mA | ~0 mA |
| Indoor siren | 0 mA | 300โ500 mA |
| Outdoor siren/bell | 0โ20 mA | 750โ2000 mA |
| Zone expander / bus module | 30โ65 mA | 65 mA |
| Cellular/IP communicator | 60โ100 mA | 250 mA (transmitting) |
The siren is the battery killer
Standby math is easy to pass and alarm math is where designs fail: an outdoor siren pulling 1.5 A will flatten a marginal battery in minutes at the exact moment you need the communicator transmitting. That's why the standard formula reserves capacity for a full alarm event after the standby period has already drained the battery.
Frequently asked questions
How is battery capacity calculated?
Ah = (standby current ร standby hours) + (alarm current ร alarm time), ร 1.25 aging factor. This calculator does exactly that.
How many hours of standby are required?
Commonly 4 h for monitored commercial, 24 h for residential/unmonitored โ but the binding number comes from the applicable standard (ULC-S304 in Canada, UL in the US) and your monitoring contract.
Why do alarm batteries fail after 3โ4 years?
SLA batteries age chemically on float charge regardless of use. Replace them proactively every 3โ5 years โ don't wait for the low-battery trouble signal during an outage.
Alarm system in Toronto or the GTA?